190 Appendix
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
14.2.10 System Modules
All system modules with diagnostics capability receive a parameter set in the form
of a record write request to the data set number or index 0x4000 or 16384.
The following attributes can be set during parameterization.
Table 158: Parameterization – Overview of the Attributes for the System Modules with Diagnostics
Capabilities (AO)
Attributes for the System Modules with Diagnostics Capabilities (PS, DIA)
-
Diagnostics
Table 159: Parameterization PS, DIA – “Diagnostics” “Transmitter or Load Voltage Lacking”
Attribute
Attribute name
Attribute value
Description
Diagnostics
No power supply, blown fuse, undervoltage or
external error
lock (false)
•
does not lead to transmission of a diagnostic
alarm nor entry in the diagnostics database of
the station proxy.
release (true)
•
leads to transmission of a diagnostic alarm.
The respective error leads to an entry in the
diagnostics database of the station proxy.
Pos: 93 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Tabelle 157: Parameterization SF, ASi 655 – “Use Empty PA Ranges” Attribute
Attribute name
Attribute value
Description
Use empty PA
ranges
None (with AS-i
2.1)
See the manual for the 75x-655 I/O module
at: www.wago.com
Analog values