98
Commissioning
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
8.6.1.6 Response to K-Bus Failure
Table 43: Parameterization DAP – Attribute Response to K-Bus Failure
Attribute Name
Attribute Value
Description
Response to K-Bus
failure
Failures in the internal communication of the
fieldbus coupler and bus terminals, e. g. missing
end terminal
PROFINET IO
communication is
stopped
*)
•
separating the cyclic connection to the
PROFINET IO controller.
input image is
cleared
•
all input informations of the respective
peripheral modules are set to zero.
input image is stored
•
the input information of the peripheral
modules immediately before the fault is
maintained.
*)
Default settings
8.6.2
Parameterization of the I/O-Modules
The configurable attributes for the various I/O module types are listed in the
appendix.
More information on the I/O module parameters!
The individual attribute values and descriptions are available in the appendix in
the respective subsections under the section “Parameters for the I/O Modules”.