24
System Description
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Pos: 18.15.5 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Systemversorgung - Ü berschrift 3 @ 3\mod_1232950096265_21.docx @ 26748 @ 3 @ 1
3.6.2
System Supply
Pos: 18.15.6 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Systemversorgung - Anschl uss @ 3\mod_1232950096796_21.docx @ 26752 @ 4 @ 1
3.6.2.1 Connection
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply.
The power supply is provided via the fieldbus coupler/controller and, if necessary,
in addition via internal system supply modules 750-613. The power supply is
reverse voltage protected.
Do not use an incorrect voltage/frequency!
The use of an incorrect supply voltage or frequency can cause severe damage to
the components.
Pos: 18.15.7 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Systemversorgung - Anschl uss - Systemversorgung ( Standar d + er wei terter ECO) @ 3\mod_1232950104031_21.docx @ 26776 @ @ 1
Figure 4: System Supply via Fieldbus Coupler/Controller (left) and via Internal System Supply
Module (right)
Table 4: Legend for Figure “System Supply via Fieldbus Coupler/Controller (left) and via Internal
System Supply Module (right)”
Position Description
1
System supply DC 24 V (-25 % … +30 %)
2
System supply 0 V
Pos: 18.15.8 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Systemversorgung - Anschl uss - Di e eing espeiste 24 V-Gleichspannung versorgt... @ 3\mod_1232950097328_21.docx @ 26756 @ @ 1
The fed DC 24 V supplies all internal system components, e.g. fieldbus
coupler/controller electronics, fieldbus interface and I/O modules via the internal
bus (5 V system voltage). The 5 V system voltage is galvanically connected to the
24 V system supply.
Pos: 18.15.9 /Serie 750 ( WAGO-I/O- SYST EM)/Systembeschrei bung/Versorgung/Systemversorgung - Anschl uss - Systemspannung (Standar d + er weiterter EC O) @ 3\mod_1232950102359_21.docx @ 26768 @ @ 1