WAGO-I/O-System 750
Device Description
41
750-370 PROFINET IO Fieldbus Coupler
Manual
Version 2.0.0
Pos: 20 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Gerätebeschreibung/Gerätebeschr eibung - Überschrift 1 @ 3\mod_1233756084656_21.docx @ 27096 @ 1 @ 1
4
Device Description
Pos: 21.1 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/Ei nlei tung/F eldbuskoppl er/-controller/Einl eitender Text/D er F eldbuskoppler 750- 0370 @ 15\mod_1371020919059_21.docx @ 122550 @ 23 @ 1
The fieldbus coupler 750-370 connects the WAGO-I/O-SYSTEM 750/753 to
PROFINET IO, the open, real-time industrial ETHERNET automation standard.
Any combination of supported digital, analog and complex I/O modules of the
WAGO-I/O-SYSTEM 750/753 can be used here.
In the context of PROFINET IO, the fieldbus coupler represents the connected
peripheral as a distributed field device and assumes the role of an IO device.
Thanks to the integrated 2-port switch it is possible to setup cost-effective line
topologies without the need for additional infrastructure components.
A DIP switch can optionally be used to address the station referring to
PROFIBUS DP devices. Thus a DCP based software tool could be unnecessary.
The diagnostic concept is fully compliant to PROFINET IO Standard IEC 61158.
Standard LEDs ensure an extensive point-of-care-testing and simplify the
commissioning of the node.
The familiar commissioning tools such as WAGO-I/O-
CHECK
can connect to the
fieldbus coupler via existent service interface.
The lines for supplying the required operating voltages are connected via the
CAGE CLAMP
®
connections.
Unsupported I/O modules!
Please note that the following I/O modules are not supported:
•
KNX/EIB/TP1 module 75x-646
•
LON
®
FTT module 75x-648
•
PROFIsafe V1 modules 750-660/000-001 and 750-665/000 001
•
Proportional Valve Module 75x-632
•
4-channel IO-Link Master 75x-657
•
CAN Gateway 75x-658.