WAGO-I/O-SYSTEM 750
Appendix 159
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 78: Submodule types and data lenghts – Digital Output Modules
PNIO module type
Process data length [byte]/
allocation [bit]
Telegram
allocation [byte]
PNIO submodule type
Data type
Input (I-PI) Output (O-PI) Input
Output
8DO (+ 8 BIT I/O), DIA in
I-PI
OctetString[2],
bit field
2
8
2
8
4
4
8DO (+24 BIT I/O), DIA in
I-PI
OctetString[4],
bit field
4
8
4
8
6
6
8DO (- 8 BIT I/O), DIA in
I-PI
-
0
8
0
8
1
1
8DO, DIA in I-PI, PE
OctetString[1],
bit field
1
8
1
8
3
3
16DO
16DO
OctetString[2],
bit field
0
0
2
16
1
3
16DO (+16 BIT O)
OctetString[4],
bit field
0
0
4
16
1
5
16DO (-16 BIT O)
-
0
0
0
16
1
1
16DO, PE
OctetString[2],
bit field
0
0
2
16
1
3
14.1.3
Digital Input/Output Modules
The module/submodule types are listed for the digital input/output modules and
the substitute I/O modules assigned in the tables below.
The subsequent tables for the submodule types and data lengths list the number of
data bits allocated in the respective process image for the individual submodules
(in bytes) and furnished with information (in bits).
The respective number of bytes of the telegrams in the send and receive direction
is also specified as input IOD
IOC (provider) and output IOC
IOD
(consumer).
There is one module type for the digital input / output modules.
Table 79: Module types – Digital Input/Output Modules
Module type
Description
Substitute I/O modules
8DIO
8-Channel Digital Input/Output Modules 75x-1502, 75x-1506
Digital input/output modules receive the provider status (IOPS) of the available
output information as well as the consumer status (IOCS) of the received input
information from the IO controller. They provide the IO controller with the
consumer status (IOCS) of the received output information as well as the provider
status (IOPS) of the available input information.