198 Appendix
WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 223: Parameterization PS, 750-606 – Attribute "Diagnosis: External fault"
Attribute Name
Attribute Value
Description
Diagnosis: External
fault
0 (false)
An external fault does not lead to transmission of a
diagnostic alarm nor entry in the diagnostics
database of the station proxy.
1 (true)
An external fault leads to transmission of a
diagnostic alarm. The respective error leads to an
entry in the diagnostics database of the station
proxy if module diagnostics is enabled.
Pos : 86 /Serie 750 ( WAGO-I/ O-SYST EM)/ Anhang/R ec ord-Datens ätz e ( Par ametrierung) (375, 377) @ 15\ mod_1369313902425_21.doc x @ 120299 @ 2 @ 1
14.3
Record Data Sets
For acyclic access, the fieldbus coupler has so-called record data sets listed in the
following table.
The table contains the index, description, access rights and addressing level of the
respective data set.
For indices 0x0000 - 0x7FFF, the PROFINET IO specification involves
manufacturer indices only used for manufacturer-specific parameterization of the
IO device.
More information on record data sets!
You can read more about special record data sets in the context of diagnostics.
The structure of standardized diagnostic data sets and channel-specific diagnostics
are explained in the chapter "Channel-Specific Diagnostics".
Table 224: Record data sets
Index
[hex]
Data set
Access
Level
2000 Parameter data, administrated by I/O module
r/w
Submodule
4000 Parameter data, administrated by fieldbus coupler
w
*)
5000
PROFIenergy parameter data, administrated by fieldbus
coupler
w
8000 ExpectedIdentificationData for one sub-slot
r
Submodule
8001 RealIdentificationData for one sub-slot
r
800A Diagnosis in channel coding
r
800B Diagnosis in all codings
r
800C Diagnosis, Maintenance, Qualified and Status
r
8010 Maintenance required in channel coding
r
8011 Maintenance demanded in channel coding
r
8012 Maintenance required in all codings
r
8013 Maintenance demanded in all codings
r
8028 RecordInputDataObjectElement
r
8029 RecordOutputDataObjectElement
r
802A PDPortDataReal
r
802B PDPortDataCheck
r/w
802C PDIRData for one subslot
r/w