WAGO-I/O-SYSTEM 750
Appendix 209
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
14.5.1.1.4 Analog Output Modules
Table 238: Fault cases of analog output modules with diagnostics capability
Item
number
Data
format
Error type
Explanation
75x-553,
75x-555,
75x-557,
75x-559,
75x-560
WORD
0x0009 / 9
Error
Output short circuit
Internal error (e.g. hardware error)
75x-562,
75x-563
WORD
0x0001 / 1
0x0002 / 2
0x0005 / 5
0x0007 / 7
0x0008 / 8
0x0011 / 17
Short circuit
Undervoltage
Overtemperature
Upper limit value
exceeded
Lower limit value
undershot
Sensor or load
voltage missing
Output short circuit
24V field power below 20V
Permissible temperature of output driver
exceeded
Configured limit value exceeded
Configured limit value undershot
Field voltage too low