100 Commissioning
WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 39: Parameterization – Overview of attributes for the station proxy (DAP)
Attributes for the station proxy (DAP)
-
Restart on K-Bus failure
-
Diagnostics of external module/channel errors
-
Internal data bus extension
-
Response to PROFINET IO failure
-
Response to K-Bus failure
-
Activation of the integrated webserver
-
Activation of the WAGO TCP service port
-
Activation of the station-wide PROFIenergy functionality
*)
*)
only for DAP with suffix "PE-DAP"
8.6.1.1
Restart on K-Bus failure
Table 40: Parameterization DAP – Attribute Restart on K-Bus failure
Attribute Name
Attribute Value
Description
Restart on K-Bus
failure
POWER ON
RESET
After any errors have been corrected can the
internal data bus be returned to operation by
resetting the fieldbus coupler's hardware or
software.
AUTORESET
The internal data bus is returned to operation
automatically after any errors have been corrected.
8.6.1.2
Diagnostics of external module/channel errors
Table 41: Parameterization DAP – Attribute Diagnostics of external module/channel errors
Attribute Name
Attribute Value
Description
Diagnostics of external
module/channel errors
0 (false)
Pending diagnostic messages are not reported to
the respective IO controller irrespective of the
submodule parameterization.
1 (true)
Pending diagnostic messages are reported to the
respective I/O controller depending on the
submodule parameterization.
8.6.1.3
Internal data bus extension
Table 42: Parameterization DAP – Attribute Internal data bus extension
Attribute Name
Attribute Value
Description
Internal data bus
extension
EEPROM-setting is
used
The settings are made according to the unlock
value saved in the EEPROM.
is not used
The internal data bus is operated at the standard
transmission rate.
is used
The internal data bus is operated at the reduced
transmission rate.