WAGO-I/O-SYSTEM 750
Commissioning 105
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 48: Send cycle time as a function of RT class, transmit clocking and scaling factor
RT class
Transmit
clocking [ms]
Scaling factor
Send cycle time [ms]
1 (RT)
1
1 (2
0
)
1
2 (2
1
)
2
4 (2
2
)
4
8 (2
3
)
8
16 (2
4
)
16
32 (2
5
)
32
64 (2
6
)
64
128 (2
7
)
128
256 (2
8
)
256
512 (2
9
)
512
3 (IRT)
1
1 (2
0
)
1
2 (2
1
)
2
4 (2
2
)
4
8 (2
3
)
8
16 (2
4
)
16
2
1 (2
0
)
2
2 (2
1
)
4
4 (2
2
)
8
8 (2
3
)
16
16 (2
4
)
32
4
1 (2
0
)
4
2 (2
1
)
8
4 (2
2
)
16
8 (2
3
)
32
16 (2
4
)
64
8.8.2
Connection Monitoring
Monitoring interval (provider data holds)
The monitoring interval is determined by the "DataHoldFactor".
If the provider data of the IO controller fail, the fieldbus coupler signals
termination of the application relationship with an RTA alarm after a specific time
(T) with the reason "DataHoldTimer expired".
The time (T) is determined as follows:
T = („DataHoldFactor“ + 1) * send cycle time