WAGO-I/O-SYSTEM 750
Diagnostics 123
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 63: Blink code table for the 'I/O' LED signaling, error code 6
Error code 6: -not used-
Error
Argument
Error Description
Solution
-
Not used
Pos : 70.15 / Serie 750 ( WAG O-I/ O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 7.. .8 (Fehlerc ode nic ht g enutz t) @ 9\mod_1281702273781_21.doc x @ 63680 @ @ 1
Table 64: Blink code table for the 'I/O' LED signaling, error code 7…8
Error code 7…8: -not used-
Error
Argument
Error Description
Solution
-
Not used
Pos : 70.16 / Serie 750 ( WAG O-I/ O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 9 ( 750-0333, -806, -842, - 843, -833) @ 9\ mod_1281702354591_21. doc x @ 63684 @ @ 1
Table 65: Blink code table for the I/O LED signaling, error code 9
Error code 9: “CPU Trap error”
Error
Argument
Error Description
Solution
1
Illegal Opcode
Fault in the program sequence.
1. Please contact the I/O Support.
2
Stack overflow
3
Stack underflow
4
NMI
Pos : 70.17 / Serie 750 ( WAG O-I/ O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 10... 11 (Fehl ercode nic ht genutzt) @ 11\ mod_1320767624985_21.doc x @ 82894 @ @ 1
Table 66: Blink code table for I/O LED signaling, error code 10…11
Error code 10…11: -not used-
Error
argument
Error description
Remedy
-
not used
-
Pos : 70.18 / Serie 750 ( WAG O-I/ O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 12 (750- 333) @ 11\mod_1320768612069_21.doc x @ 82958 @ @ 1
Table 67: Blink code table for I/O LED signaling, error code 12
Error code 12 “Initialization error, internal bus”
Error
Argument
Error description
Remedy
n*
Error with parameter
communication during
internal bus initialization
1. Switch off the power for the node.
2. Ensure that the nth module with process data is
supplied with power at the field side.
3. Switch the power on.
* The number of light pulses (n) indicates the position of the I/O module.
I/O modules without data are not counted (e.g. supply modules without diagnostics)
Pos : 70.19 / Serie 750 ( WAG O-I/ O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Vers orgungss pannungsst at us aus werten ( alle Koppler/C ontroll er) @ 6\ mod_1259230026625_21.doc x @ 45546 @ 3 @ 1