WAGO-I/O-SYSTEM 750
Appendix 151
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Pos : 83 /All e Seri en (Allgemei ne Module)/Ü berschrif ten f ür alle Serien/Anhang - Ü bersc hrift 1 @ 4\ mod_1239874070437_21.doc x @ 30560 @ 1 @ 1
14
Appendix
Pos : 84 /Serie 750 ( WAGO-I/ O-SYST EM)/F unktions beschr eibung/Pr ozes sabbild/M odul- und Submodulz uor dnung der Bus kl emmen -T abellen ( 750-375, - 377) @ 13\ mod_1354694858584_21.doc x @ 107370 @ 2333333444444444444444434 @ 1
14.1
Module and Submodule types of the I/O-Modules
14.1.1
Digital Input Modules
The module/submodule types are listed for the digital input modules and the
substitute I/O modules assigned in the tables below.
The subsequent tables for the submodule types and data lengths list the number of
data bits allocated in the respective process image for the individual submodules
(in bytes) and furnished with information (in bits).
The respective number of bytes of the telegrams in the send and receive direction
is also specified as input IOD
IOC (provider) and output IOC
IOD
(consumer).
The group of digital input modules is divided into eight module types.
Table 75: Module types – Digital Input Modules
Module type
Description
Substitute I/O modules
1DI, DIA
1-Channel Digital Input Modules,
1 bit diagnostics
75x-435
2DI
2-Channel Digital Input Modules
75x-400, 75x-401, 75x-405,
75x-406, 75x-407, 75x-410,
75x-411, 75x-412, 75x-413,
75x-416, 75x-427, 75x-429,
75x-438
2DI, DIA
2-Channel Digital Input Modules,
1 bit diagnostics per channel
75x-419, 75x-421, 75x-425
2DI, DIA, Ackn.
2-Channel Digital Input Modules,
1 bit diagnostics per channel,
1 bit diagnostics confirmation per channel
75x-418
4DI
4-Channel Digital Input Modules
75x-402, 75x-403, 75x-408,
75x-409, 75x-414, 75x-415,
75x-422, 75x-423, 75x-424,
75x-428, 75x-432, 75x-433,
75x-440, 75x-1420,
75x-1421,75x-1422,
75x-1423
8DI
8-Channel Digital Input Modules
75x-430, 75x-431, 75x-434,
75x-436, 75x-437,
75x-1415, 75x-1416,
75x-1417, 75x-1418
8DI, DIA, DIA DIS
8-Channel Digital Input Modules,
1 bit diagnostics per channel,
1 bit diagnostics disabling per channel
750-439
8DI, DIA, DI DIS
8-Channel Digital Input Modules,
1 bit diagnostics per channel,
1 bit input disabling per channel
750-1425
16DI
16-Channel Digital Input Modules
750-1400, 750-1402, 75x-1405
75x-1406, 75x-1407, 75x-1408
Digital input modules receive the consumer status (IOCS) as process data