164 Appendix
WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
14.1.6.2 2-Channel Pulse Width Modules
The group of 2-channel pulse width output module has one module type divided
into two submodule types.
Table 87: Module types – 2-Channel Pulse Width Output Modules
2PWM
Module type
Description
Substitute I/O modules
2PWM
2-Channel Pulse Width Output Modules,
16 bits output data per signal channel
75x-511,
plus all variations
Pulse width output modules receive the provider status (IOPS) from the IO
controller and supply it with the consumer status (IOCS) of the received output
information in case only the actual user data is exchanged. If all existing
information is available in the process image of the inputs and outputs, the process
data qualifiers are also transmitted in the opposite direction.
Table 88: Submodule types and data lengths – 2-Channel Pulse Width Output Module
PNIO module type
Process data length [byte]/
allocation [bit]
Telegram
allocation [byte]
PNIO submodule type
Data type
Input (I-PI) Output (O-PI) Input
Output
2PWM
INT16[2] O
Integer16
0
4
1
5
{UINT8, INT16}[2] I/O
{Unsigned8,
Unsigned16}
6
6
8
8
14.1.6.3 Distance and Angle Measurement Modules
The group of distance and angle measurement modules includes three module
types:
Table 89: Module types – Distance and Angle Measurement Modules
Module type
Description
Substitute I/O modules
1SSI
SSI Transmitter Interface,
32 bits input data
75x-630,
plus all variations
Module type
Description
Substitute I/O modules
1ENC
Incremental Encoder Interface,
32 bits input and output data plus control byte
and status byte per signal channel, access to the
register structure via cyclic data exchange
75x-631, 75x-634, 75x-637,
plus all variations
Module type
Description
Substitute I/O modules
1DII
Digital Impulse Interface,
24 bits input and output data plus control byte
and status byte per signal channel, access to the
register structure via cyclic data exchange
75x-635
For the distance and angle measurement modules, the provider and consumer
status (IOPS, IOCS) of the input or output information are exchanged between the
IO controller and IO device in both directions. With the SSI interface 75x-630,
there is also an option to transmit the input data of the transmitter only.