WAGO-I/O-SYSTEM 750
Appendix 165
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
In this case, the IO device only receives the consumer status (IOCS) from the IO
controller and supplies it with the provider status (IOPS) of the available input
data.
Table 90: Submodule types and data lengths – Distance and Angle Measurement Modules
PNIO module type
Process data length [byte]/
allocation [bit]
Telegram
allocation [byte]
PNIO submodule type
Data type
Input (I-PI) Output (O-PI) Input
Output
1SSI
UINT32 I
Unsigned32
4
0
5
1
{UINT8, UINT8,
UINT32} I/O
{Unsigned8,
Unsigned8,
Unsigned32}
6
6
8
8
1ENC
{UINT8, INT16} I/O
{Unsigned8,
Integer16}
6
6
8
8
1DII
{UINT8, UINT8[3]} I/O
{Unsigned8,
Unsigned8[3]}
4
4
6
6
14.1.6.4 Serial Interfaces
The group of serial interfaces has two module types divided into seven submodule
types.
Table 91: Modultypen – Serial Interfaces
Module type
Description
Substitute I/O modules
1SER
Serial Interfaces
75x-650, 75x-651, 75x-653,
75x-652,
plus all variations
Module type
Description
Substitute I/O modules
DXCH
Data Exchance Modules
75x-654
For the serial interfaces, the provider and consumer status (IOPS, IOCS) of the
input or output information are exchanged between the IO controller and IO
device in both directions.
Table 92: Submodule types and data lengths – Serial Interfaces
PNIO module type
Process data length [byte]/
allocation [bit]
Telegram
allocation [byte]
PNIO submodule type
Data type
Input (I-PI) Output (O-PI) Input
Output
1SER
{UINT8, UINT8[3]} I/O
{Unsigned8,
Unsigned8[3]}
4
4
6
6
{UINT8, UINT8[5]} I/O
{Unsigned8,
Unsigned8[5]}
6
6
8
8
{UINT8, UINT8,
UINT8[6]} I/O
{Unsigned8,
Unsigned8,
Unsigned8[6]}
8
8
10
10
{UINT8, UINT8,
UINT8[22]} I/O
{Unsigned8,
Unsigned8,
Unsigned8[22]}
24
24
26
26