WAGO-I/O-SYSTEM 750
Appendix 173
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 113: Parameterization – Overview of Attributes for Digital Input Modules with Diagnostics
(DI, DIA)
Attributes for Digital Input Modules with Diagnostics (DI, DIA)
-
Channel diagnosis
-
Diagnosis: External fault
Table 114: Parameterization DI, DIA – Attributes "Channel diagnosis"
Attribute Name
Attribute Value
Description
Channel diagnosis
0 (false)
Any errors that may occur on the respective signal
channel do not cause transmission of a diagnostic
alarm nor entry in the diagnostics database of the
station proxy.
1 (true)
Any errors that may occur on the respective signal
channel and the error type explicitly released entail
transmission of a diagnostic alarm. The respective
error leads to an entry in the diagnostics database
of the station proxy.
Table 115: Parameterization DI, DIA – Attributes "Diagnosis: External fault"
Attribute Name
Attribute Value
Description
Diagnosis: External
fault
0 (false)
An external error on the respective signal channel
does not cause transmission of a diagnostic alarm
nor entry in the diagnostics database of the station
proxy.
1 (true)
Provided that the channel diagnostics of the
respective signal channel has been activated, an
external error leads to transmission of a diagnostic
alarm and entry in the diagnostics database of the
station proxy.