WAGO-I/O-SYSTEM 750
Appendix 197
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 219: Parameterization PS, DIA – Attribute "Module diagnosis"
Attribute Name
Attribute Value
Description
Module diagnosis
0 (false)
An error does not lead to transmission of a
diagnostic alarm nor entry in the diagnostics
database of the station proxy.
1 (true)
The respective error leads to an entry in the
diagnostics database of the station proxy if module
diagnostics is enabled. An error leads to
transmission of a diagnostic alarm. The respective
error leads to an entry in the diagnostics database
of the station proxy.
Table 220: Parameterization PS, DIA – Attribute "Sensor or load voltage missing"
Attribute Name
Attribute Value
Description
Sensor or load voltage
missing
0 (false)
Absence of the power supply does not lead to
transmission of a diagnostic alarm nor entry in the
diagnostics database of the station proxy.
1 (true)
Absence of the power supply leads to transmission
of a diagnostic alarm. The respective error leads to
an entry in the diagnostics database of the station
proxy if module diagnostics is enabled.
Table 221: Parameterization PS, 750-610, 750-611 – Attribute "Diagnosis: Fuse blown/open"
Attribute Name
Attribute Value
Description
Diagnosis: Fuse
blown/open
0 (false)
A defective fuse does not lead to transmission of a
diagnostic alarm nor entry in the diagnostics
database of the station proxy.
1 (true)
A defective fuse leads to transmission of a
diagnostic alarm. The respective error leads to an
entry in the diagnostics database of the station
proxy if module diagnostics is enabled.
Table 222: Parameterization PS, 750-606 – Attribute "Diagnosis: Undervoltage"
Attribute Name
Attribute Value
Description
Diagnosis:
Undervoltage
0 (false)
An undervoltage does not lead to transmission of a
diagnostic alarm nor entry in the diagnostics
database of the station proxy.
1 (true)
An undervoltage leads to transmission of a
diagnostic alarm. The respective error leads to an
entry in the diagnostics database of the station
proxy if module diagnostics is enabled. An
undervoltageg leads to transmission of a diagnostic
alarm. The respective error leads to an entry in the
dagnostics database if module diagnostics is
enabled.