WAGO-I/O-SYSTEM 750
Appendix 201
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 226: Data set I&M 1
N
Octet N Octet N+1
Meaning generally
Meaning for the fieldbus coupler
0
0x00
0x21
Block type
Block type
2
0x00
0x38
Block length (without
header)
Block length = 56 Byte
4
0x01
0x00
Block version
Block version 1.0
6
?
?
I&M function
(visible string,
length 32 bytes)
User-specific function description filled
out with blanks.
… …
…
36 ?
?
38 ?
?
I&M location
(visible string,
length 22 bytes)
User-specific location for installation
filled out with blanks.
… …
…
58 ?
?
Table 227: Data set I&M 2
N
Octet N Octet N+1
Meaning generally
Meaning for the fieldbus coupler
0
0x00
0x22
Block type
Block type
2
0x00
0x12
Block length (without
header)
Block length = 18 Byte
4
0x01
0x00
Block version
Block version 1.0
6
?
?
I&M function
(visible string,
length 16 bytes)
User-specific installation date filled out
with blanks.
The date ist formatted as follows:
“YYYY-MM-DD HH:MM”
… …
…
20 ?
?
Table 228: Data set I&M 3
N
Octet N Octet N+1
Meaning generally
Meaning for the fieldbus coupler
0
0x00
0x23
Block type
Block type
2
0x00
0x38
Block length (without
header)
Block length = 56 Byte
4
0x01
0x00
Block version
Block version 1.0
6
?
?
I&M description
(visible string,
length 54 bytes)
User-specific description filled out with
blanks.
… …
…
58 ?
?
Table 229: Data set I&M 4
N
Octet N Octet N+1
Meaning generally
Meaning for the fieldbus coupler
0
0x00
0x24
Block type
Block type
2
0x00
0x38
Block length (without
header)
Block length = 56 Byte
4
0x01
0x00
Block version
Block version 1.0
6
?
?
I&M signature
(visible string,
length 54 bytes)
User-specific security code filled out with
blanks.
… …
…
58 ?
?
Pos : 88.1 /Serie 750 (WAGO-I/ O-SYST EM)/ Anhang/ Kanalspezifisc he Diag nose 1. 1 ( 750-375, - 377) @ 15\ mod_1369748055770_21.doc x @ 120790 @ 23 @ 1