WAGO-I/O-SYSTEM 750
Appendix 211
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
14.5.1.1.6 PROFIsafe V2 iPar I/O Modules
Item number:
75x-661/000-003,
75x-662/000-003,
75x-663/000-003,
75x-666/000-003,
75x-667/000-003
The fault cases of the PROFIsafe V2 iPar I/O modules are described in detail in
the manuals for the respective I/O modules.
More information on the PROFIsafe V2 iPar I/O modules!
Detailed information on the PROFIsafe V2 iPar I/O modules and their fault case
descriptions is available in the I/O module manuals. They are available to
download from the WAGO website at: www.wago.com.
14.5.2
Difference between Real and Expected Configuration
The fieldbus coupler provides diagnostic information in the event of module
differences in the form of a "ModuleDiffBlock" when there are deviations
between the module/submodule configuration of the IO controller and the IO
modules actually connected.
The "BlockType" in the head structure of the data set corresponds to the value for
module differences (0x8104). The length gives information on the differences
between the configured and connected modules/submodules.
The "ModuleDiffBlock" is initiated with the following head structure.
Table 240: Initial structure "ModuleDiffBlock"
Byte
offset
Data type
Description
0 / 1
WORD
0x00
0x01 Number of available APIs = 1
2 / 3
DWORD
0x00
0x00
API (Application Process Instance) = 0
4 / 5
0x00
0x00
6 / 7
WORD
Number of slots with differences between real and
expected configuration
Depends on the amount of following entries
The entries for the incorrectly configured modules/submodules then follow. The
number of existing entries is stored in the preliminary structure of the
"ModuleDiffBlock".