WAGO-I/O-SYSTEM 750
Appendix 213
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 242: Structure of the erroneously configured submodules
Byte
offset
Data type
Description
0 / 1
WORD
0x00
0x01
Subslot with odd submodule
2 / 3
DWORD
0x00
0x00
Identification of the plugged submodule
(SubmoduleIdentNumber)
4 / 5
0x00
0x00
6 / 7
WORD
Submodule state (Submodulstate.b15 = 0)
0x0000
No submodule present
0x0001
Wrong submodule
0x0002
Submodule locked by IO controller
0x0003
Reserved
0x0004
Application ready pending
0x0005
Reserved
0x0006
Reserved
0x0007
Submodule substituted
0x0008
...
0x7FFF
Reserved
8 / 9
WORD
Submodule state (Submodule state.b15 = 1)
b0
…
b2
'000'
'001'
'010'
…
'111'
---
The submodule is not available for takeover
by IOSAR.
Reserved
b3
0
1
No channel of the submodule contains
"QualifiedChannelDiagnosis".
At least one channel of the submodule
contains "QualifiedChannelDiagnosis".
b4
0
1
No channel of the submodule requires
maintenance.
At least one channel of the submodule
demands maintenance.
b5
0
1
No channel of the submodule demands
maintenance.
At least one submodule channel demands
maintenance.
b6
0
1
There is no diagnosis data available/stored for
this submodule.
There is diagnosis data available for this
submodule: It can be read with the
corresponding records.