WAGO-I/O-SYSTEM 750
Device Description
57
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
Table 28: Technical Data – Internal Bus
Data contacts
slide contact, hard gold plated, self-
cleaning
Pos : 44 /Serie 750 ( WAGO-I/ O-SYST EM)/ Ger ät ebesc hrei bung/T echnisc he Daten/ Kli matische U mwelt beding ung en/Technisc he Daten Klimatisc he U mweltbedingungen m. erw. T empbereic h; - 20...+ 60°C/-40. ..+ 85° C f ür / 025 @ 5\ mod_1247658089120_21. doc x @ 37606 @ 3 @ 1
4.6.6
Climatic Environmental Conditions
Table 29: Technical Data – Climatic environmental conditions
Operating temperature range
0 °C … 55 °C
Operating temperature range for
components with extended
temperature range (750-xxx/025-xxx)
-20 °C … +60 °C
Storage temperature range
-25 °C … +85 °C
Storage temperature range for
components with extended
temperature range (750-xxx/025-xxx)
-40 °C … +85 °C
Relative humidity
max. 5 % … 95 % without condensation
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are
taken, which are used in an environment
involving:
– dust, caustic vapors or gases
– ionizing radiation
Pos : 45 /D okument ation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0. doc x @ 21810 @ @ 1