5.5
Mounting Sequence
Fieldbus couplers/controllers and I/O modules of the WAGO-I/O-SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard EN
50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler/controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos : 57.8 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Vorsic ht/ Vorsicht: Verl etz ungsgefahr durc h s charf kantige M ess er kont akt e! @ 6\ mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
Pos : 57.9 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Achtung/Achtung: Bus kl emmen nur in vorgesehener R eihenfolg e st ec ken! @ 6\ mod_1256194177073_21. doc x @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the top.
This mechanical coding helps to avoid configuration errors, which may destroy
the I/O modules. Therefore, insert I/O modules only from the right and from the
top.
Pos : 57.10 / Serie 750 ( WAG O-I/ O-SYST EM)/ Wichtig e Erl äuter ung en/Sic her hei ts- und s onstige Hinweise/Hinweis/Hi nweis : Bus absc hluss nic ht vergessen! @ 6\ mod_1256194225557_21.doc x @ 43432 @ @ 1
Don't forget the bus end module!
Always plug a bus end module 750-600 onto the end of the fieldbus node! You
must always use a bus end module at all fieldbus nodes with WAGO-I/O-
SYSTEM 750 fieldbus couplers/controllers to guarantee proper data transfer.
Pos : 57.11 /D okument ati on allgemei n/Gli ederungsel ement e/---Seit enwec hs el--- @ 3\ mod_1221108045078_0. doc x @ 21810 @ @ 1