This chapter describes the essential functions of the fieldbus coupler.
•
Device start-up and initialization
•
Switch port settings
•
Identification and maintenance data sets (I&M)
•
Process data structure
•
Configuration limits
•
Flexible configuration of digital I/O modules
•
Variation of physical peripheral layout
•
Sharing I/O modules in several ARs (Shared Device)
•
Use of failsafe I/O modules (PROFIsafe V2)
•
Individual parameterization of I/O modules using iPar-Server
•
Control of digital and analog output modules by means of PROFIenergy
•
Firmware Update
Pos : 63.2 /Serie 750 (WAGO-I/ O-SYST EM)/F unktions beschr eibung/Funkti onsbesc hrei bung St ations hochl auf- und I niti alisierung 750-375, - 377 - T eil 1. 1 @ 15\ mod_1370510165464_21.doc x @ 122000 @ 2 @ 1
7.1
Device Start-Up and Initialization
After a restart the fieldbus coupler does several hardware tests, e.g. the check of
memory components. Successfully passed those tests it initializes the internal
communication system K-Bus to identify the arranged I/O modules and to
exchange information with them. This phase is indicated by the I/O LED, which
flashes red at 10 Hz. Subsequent to the successful K-Bus initialization the I/O-
LED changes to green on-state.
The fieldbus coupler then switches to the "Fieldbus Start" state in which it waits
for the connection with the higher-level control system (IO controller) as an IO
device.
If an error occurs during start-up, the I/O LED flashes red and a blink code
indicates the respective error message.