98
Commissioning
WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Manual
Version 1.1.0
5.
Adapt the global station settings at the DAP submodule of the fieldbus
coupler if necessary (see also the chapter „Parameterization of the Station
Proxy (DAP).”
6.
Adapt the module or submodule parameterization of the configured I/O
modules if necessary
(see also the chapter „Parameterization of the I/O Modules”).
7.
Select the communication class RT_CLASS_1 (RT) oder RT_CLASS_3
(IRT) at the interface submodule of the fieldbus coupler. In case of IRT the
fieldbus coupler becomes SYNC slave. Using IRT operation adapt the name
of the SYNC domain if necessary.
8.
Check the update time or the send cycle and the monitoring time of the
connection to the IO controller and adapt the settings if necessary.
9.
If the station is part of an media redundant network (ring structure) assign
the MRP client role to the fieldbus coupler and adapt the name of the MRP
domain if necessary.
10. Check the connection settings at the port submodules of the fieldbus coupler
and adapt these if necessary
(see also the chapter „Port Configuration”).
11. Build the expected network topology using on-board means of the
engineering tool. This is mandatory if the fieldbus coupler runs within an
IRT domain. The IO device replacement without using any tool is also only
possible if the expected network topology is known to the IO controller. On
match of expected and real network topology it is possible to pass on the
tool based station name assignment even during the first commissioning.
12. Switch on the fieldbus coupler power supply
(see also the chapter „Device Start-Up and Initialization”).
13. Alternative to the topology based station name assignment the station name
can be set by a DCP tool (see also the chapter „DCP“) or be defined using
the available DIP switch
(see also the chapter „DIP switch“).
14. Upload the system data subsequently onto the IO controller.
After a successful connection establishment between the IO controller and the IO
device the state of productive data exchange is entered.
Pos : 65.2 /Serie 750 (WAGO-I/ O-SYST EM)/I n Betrieb nehmen/ Fel dbus knoten i n Betrieb nehmen/ PRO FIBU S/ GSD-D at eien ( 750-375, - 377) @ 14\ mod_1364233656793_21.doc x @ 116020 @ 2 @ 1