WAGO-I/O-SYSTEM 750
Commissioning 55
750-496 8AI 0/4-20mA S.E.
Manual
Version
1.2.2
Table 28:
Channel settings
Menu Item
Option
Description
Show measurement
underrange
*)
The “Measurement Underrange” diagnosis function is activated
and is displayed in the status byte.
The “Measurement Underrange” diagnostics function is
deactivated and is not displayed in the status byte.
Show overrange of user
range values
*)
The “User limiting value overrange” diagnosis function is
activated and is displayed in the status byte.
The “User limiting value overrange” diagnosis function is
deactivated and is not displayed in the status byte.
Show underrange of
user range values
*)
The “User limiting value underrange” diagnosis function is
activated and is displayed in the status byte.
The “User limiting value underrange” diagnosis function is
deactivated and is not displayed in the status byte.
Show short circuit
*)
The “Display short circuit” diagnosis function is activated and is
displayed in the status byte.
The “Display short circuit” diagnosis function is deactivated and
is not displayed in the status byte.
Show wire break
*)
The “Show wire break” is activated and is displayed in the status
byte.
The “Show wire break” diagnosis function is deactivated and is
not display status byte.
Specifying Limiting Values
Upper limit
Enter the upper limiting value of your required value range.
The value entered must fall within the value range −32768 … +32767.
Lower limit
Enter the lower limiting value of your required value range.
The value entered must fall within the value range −32768 … +32767.
Offset for Measurement Range Monitoring
Offset for diagnosis
measurement overrange
Enter the offset value at which the “Measurement Range Overrange”
diagnostic message should be triggered.
Note: When selecting the sensor type 3.6 … 21mA (NAMUR NE43), you
are not permitted to determine this value.
Offset for diagnosis
measurement
underrange
Enter the offset value at which the “Measurement Range Underrange”
diagnostic message should be triggered.
Note: When selecting the sensor type 3.6 … 21mA (NAMUR NE43), you
are not permitted to determine this value.
*)
Factory setting
7.1.1.4.3 “Scaling” Menu Item
Save settings!
Click the
[Write]
or
[Write all
]
button to write any settings you have made to the
I/O module.