WAGO-I/O-SYSTEM 750
Commissioning 57
750-496 8AI 0/4-20mA S.E.
Manual
Version
1.2.2
Table 29:
Scaling
Menu Item
Option
Description
Channel x
Activate factory scaling
Factory scaling is activated (no effect).
*)
Factory scaling is deactivated (no effect).
Gain
The Gain value is specified by the manufacturer.
Offset The Offset value is specified by the manufacturer.
Activate user scaling
User-defined scaling is active. By activating this setting you can
also specify the individual gain and offset values.
*)
User scaling is deactivated. Individually specified gain and offset
values cannot be entered.
Gain
Enter the Gain value for the user scaling.
The Gain value is used as a gain factor on the process value.
The value entered must fall within the value range 0 … 65535.
The resolution is 1/1024.
Offset
Enter the Offset value for the user scaling.
The Offset value causes a zero offset of the process value (shift
along the Y axis).
The value entered must fall within the value range
−32768 … 32767.
Current [mA]
Display of the calibrated input current in milliamps (mA).
This is a 32-bit value.
If the channel is deactivated, “N/A” (not available) is displayed.
The input current value is read cyclically from the I/O module.
Process value (dec)
Display of the process value for the channel selected in decimal notation.
If the channel is deactivated, “N/A” (not available) is displayed.
The process value is read cyclically from the I/O module.
Process value (hex)
Display of the process value for the channel selected in hexadecimal
notation.
If the channel is deactivated, “0x7FFF” (not available) is displayed.
The process value is read cyclically from the I/O module.
*)
Factory setting