750-585 [2 AO 0-20 mA EEx i]
•
7
View
WAGO-I/O-SYSTEM 750
I/O Modules
2 I/O Modules
2.1 Analog Output Modules
2.1.1 750-585 [2 AO 0-20 mA EEx i]
2-Channel Analog Output Module (0-20 mA EEx i)
2.1.1.1 View
13 14
-
A1 A2
S
S
750-585
15 16
-
Function
AO 1
Function
Data contacts
0 V
AO 2
Power jumper contacts
AO 1
AO 2
Shield
(screen)
Shield
(screen)
Fig. 2.1.1-1: 2-Channel Analog Output Module 750-585
g058500e
2.1.1.2 Description
The analog output module 750-585 creates intrinsically safe standardized
signals of 0-20 mA in the hazardous area of Zone 1.
The installation of the WAGO-I/O-SYSTEM 750 is to be done in zone 2 or in
non-hazardous environments.
The module has two output channels and enables, for example, the direct
wiring of two 2-conductor actuators to the connections AO 1 and 0V or AO 2
and 0V. The intrinsically safe signals are transmitted via AO 1 or AO 2.
The input channels of a module have a common ground and a shield (screen)
connection (S). The Shield (screen) is directly connected to the DIN rail. A
capacitive connection is made automatically when snapped onto the DIN rail.
The Output signal of each channel is electrically isolated and will be
transmitted with a resolution of 12 bits.
The operational readiness and trouble-free internal data bus communication of
the channels are indicated via a green Function LED.