8
•
750-585 [2 AO 0-20 mA EEx i]
Description
WAGO-I/O-SYSTEM
750
I/O
Modules
Any configuration of the output modules is possible within an intrinsically
safe segment when designing the fieldbus node. Grouping of module types is
not necessary.
Attention
An additional supply module 750-625, DC 24 V EEx i must be added for the
approved intrinsically safe field side supply voltage of 24 V.
Supply principle:
625
435
535
485
EEx i
EEx i
EEx i
EEx i
EEx i
585
24 V
24 V
24 V
Fieldbus Coupler/ Controller
I/O Modules
End
module
Electronic
Field
Field
Potential 2
Potential 1
The supply voltage for the field side is made automatically through the
individual I/O modules by means of power jumper contacts.
Note
If the employment of further DC 24 V EEx i Supply modules is necessary for
reasons of extent of utilization, four Separation modules (750-616) must
guarantee the distance between the intrinsically safe segments.
The analog output module 750-585 can be used with all couplers/controllers
of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, -
323,
-324 and -327).
Further Information
General information to the explosion prevention is in the manual chapter
„Use in Hazardous Environments“ described!