WAGO I/O System 750 XTR
Device Description 27
750-600/040-001 End Module with Potential Group XTR
Manual
Version 1.0.1
Table 15: EMc – Testing Standards: Emission of Interference
Standard
Test Value
*)
Enclosure Emission of Interference
• EN 55016-2-3
30 dB(µV/m), QP, 30 MHz … 230 MHz
37 dB(µV/m), QP, 230 MHz … 1 GHz
70 dB(µV/m), Peak, 1 GHz … 3 GHz
50 dB(µV/m), AV, 1 GHz … 3 GHz
74 dB(µV/m), Peak, 3 GHz … 6 GHz
54 dB(µV/m), AV, 3 GHz … 6 GHz
• EN 55011 Class A
• EN 55016-2-3
40 dB(µV/m), QP, 30 MHz … 230 MHz
47 dB(µV/m), QP, 230 MHz … 1 GHz
76 dB(µV/m), Peak, 1 GHz … 3 GHz
56 dB(µV/m), AV, 1 GHz … 3 GHz
80 dB(µV/m), Peak, 3 GHz … 6 GHz
60 dB(µV/m), AV, 3 GHz … 6 GHz
• Shipbuilding
**)
(Class B)
80
dB(μV/m)
…52
dB(μV/m),
QP,
150 kHz … 300 kHz
52
dB(μV/m)
… 34
dB(μV/m),
QP,
0.3 MHz … 30 MHz
54
dB(μV/m),
QP, 30 MHz … 2.0 GHz
54
dB(μV/m),
AV, 1.0 GHz … 6.0 GHz
24
dB(μV/m),
QP, 156 MHz … 165 MHz
• Shipbuilding
**)
(Class A)
80
dB(μV/m)
… 50
dB(μV/m),
QP,
150 kHz … 30 MHz
60
dB(μV/m)
… 54
dB(μV/m),
QP,
30 MHz … 100 MHz
54
dB(μV/m),
QP, 100 MHz … 2.0 GHz
54
dB(μV/m),
AV, 1.0 GHz … 6.0 GHz
24
dB(μV/m),
QP, 156 MHz … 165 MHz
Conducted Emission of Interference – Line Connection AC Voltage
• EN 55016-2-1
Standard not applicable
• EN 55011 Class A
• EN 55016-2-1
Standard not applicable
Conducted Emission of Interference – Line Connection
• Shipbuilding
**)
(Class B)
96 dB(µV) … 50 dB(µV), 10 kHz … 150 kHz
60 dB(µV) … 50 dB(µV), 150 kHz … 350 kHz
50 dB(µV), 0,35 MHz … 30 MHz
• Shipbuilding
**)
(Class A)
120 dB(µV) … 69 dB(µV), 10 kHz … 150 kHz
79 dB(µV), 150 kHz … 500 kHz
73 dB(µV), 0.5 MHz … 30 MHz
Conducted Emission of Interference – Line Connection DC Voltage
• EN 55016-2-1
Standard not applicable
Conducted Emissions – Wired Network Ports
• EN 55032 Class A
53 dB(μA) … 43 dB(μA) QP,
0.15 MHz ... 0.5 MHz
40 dB(μA) … 30 dB(μA) AV,
0.15 MHz ... 0.5 MHz
43 dB(μA) QP, 0.
5 MHz ... 30 MHz
30 dB(μA) AV, 0.
5 MHz ... 30 MHz