18 Device Description
WAGO I/O SYSTEM 750 XTR
750-624/040-00x Field Supply Filter 24 VDC HI XTR
Manual
Version 1.4.0
3.2.2
Power Jumper Contacts/Field Supply
The 750-624/040-00x I/O module has two self-cleaning power contacts that
transmit power for the field side.
These contacts are located on the right side of the I/O module are designed as
spring contacts.
Variant /040-000 also has power contacts for providing power to the field supply.
These contacts are located on the left side of the I/O module are designed as
power jumper contacts.
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
3.2.2.1 Variant 750-624/040-000
Figure 3: Power Jumper Contacts
Table 5: Legend for Figure “Power Jumper Contacts”
Contact
Type
Function
1
Spring contact Potential transmission (U
v
) for field supply
2
Spring contact Potential transmission (0 V) for field supply
3
Blade contact Potential feed-in (0 V) for field supply
4
Blade contact Potential feed-in (U
v
) for field supply