WAGO I/O SYSTEM 750 XTR
Device Description 23
750-633/040-000 Up/Down Counter Ex i XTR
Manual
Version 1.1.0
3.6.4
Inputs
Table 10: Technical Data – Inputs
Number of inputs
2
• U/D (Gate)
• CLOCK
Sensor supply U
V
8.2 VDC
Signal current (0)
≤ 1.2
mA
Signal current (1)
≥ 2.1
mA
Input filter
10 µs
Switching hysteresis
0.2 mA
Open-circuit voltage
8.2 VDC
Input resistance
1
kΩ
Short-circuit current
8.2
mA (+5 … −5
%)
Input pulse length
≥ 10
µs
Input pulse separation
≥ 10
µs
3.6.5
Output
Table 11: Technical Data – Outputs
Number of outputs
1
Open-circuit voltage
24 VDC
Internal resistance R
i
285
Ω
3.6.6
Communication
Table 12: Technical Data – Communication
Bit width
1 × 32 bits data;
1 × 8 bits status/diagnostics