30 Device Description
WAGO I/O SYSTEM 750 XTR
750-633/040-000 Up/Down Counter Ex i XTR
Manual
Version 1.1.0
Table 21: Climatic and Mechanical Environmental Conditions and Shipbuilding
Standard
Test Value
Transport
EN 60870-2-2
Ct2(2k4) (except precipitation/water/moisture)
Mechanical Environmental Conditions
EN 61850-3
Achieved
EN 60870-2-2
Bm
EN 60721-3-1
1M3
EN 60721-3-3
3M5
EN 60068-2-6
Acceleration 5g
IEC 60068-2-27 Shock
15g, 11 ms, 1000 shocks per axis and
direction, half-sine
25g, 6 ms, 1000 shocks per axis and direction,
half-sine
Environmental Requirements
EN 61850-3
Achieved
EN 60721-3-1
1K5 (except precipitation and ice formation)
EN 60721-3-3
3K7 (except wind-driven precipitation, water
and ice formation)
EN 60870-2-2
C3 (except wind-driven precipitation and ice
formation)
Shipbuilding (Mechanical/Climatic Environmental Conditions and EMC)
Shipbuilding
*)
Temperature:
D (cold test with −40 °C/16
h)
Humidity:
B
Vibration:
B (vibration test with
acceleration amplitude 5.0g)
EMC:
B
Enclosure: A
*)
The list of ship certifications issued is available in the section “Approvals”.