WAGO I/O SYSTEM 750 XTR
Mounting 47
750-633/040-000 Up/Down Counter Ex i XTR
Manual
Version 1.1.0
2.
Press the I/O module into the assembly until the I/O module snaps into the
carrier rail.
Figure 8: Snap the I/O Module into Place (Example)
With the I/O module snapped in place, the electrical connections for the data
contacts and power jumper contacts (if any) to the fieldbus coupler/controller or
to the previous or possibly subsequent I/O module are established.
5.2.2
Removing the I/O Module
1.
Remove the I/O module from the assembly by pulling the release tab.
Figure 9: Removing the I/O Module (Example)
Electrical connections for data or power jumper contacts are disconnected when
removing the I/O module.