38 Process Image
WAGO I/O System 750
750-637 Incremental Encoder Interfaces
Manual
Version 1.6.1
Public
Table 29: Status Byte S0, Version 750-637/000-004
Status Byte S0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
PF
AckSet
LoadExt
OUF
Enable_
Cam_
Ack
CNT-SET_
ACK
LAT_
EXT_
VAL
LATC_
VAL
LATC_VAL
Ack Bit for EN-LATC (C0.0)
Latch Mode: This bit is set on a positive edge at input C
Reset is carried out when EN_LATC is reset
Preload Mode: This bit is set on a positive edge at input C
Reset is carried out when EN_LATC is reset
LAT_EXT_VAL
Ack Bit for EN-LAT_EXT (C0.1)
Latch Mode: This bit is set on a positive edge at the Latch input
Reset is carried out when EN_LAT_EXT is reset
Preload Mode: This bit is set on a positive edge at the Latch input
Reset is carried out when EN_LAT_EXT is reset
CNT-SET_ACK
Ack Bit for CNT_SET (C0.2)
−
Reset is carried out when CNT_SET=0.
Enable_Cam_Ack
Ack Bit for Enable_Cam (C1.6)
−
The command has been executed by the I/O module
when the ack bit and the request bit are identical.
The cam outputs have the desired state.
OUF
Combined Overflow/Underflow Status Bit
Underflow function (“counter-clockwise” rotation)
1:
On counter underflow from 0x00000000 to 0xffffffff
0:
When counter v
alue is then < 0xAAAAAAAA
On acknowledgement, i.e., positive edge RESET_OUF
(C0.4)
With an overflow event without previous
acknowledgement
Overflow function (“clockwise” direction of rotation)
1:
On counter overflow from 0xffffffff to 0x00000000
0:
When counter value is then < 0x55555555
On acknowledgement, i.e., positive edge RESET_OUF
(C0.4)
For underflow event without previous acknowledgement
AckSet LoadExt
Ack Bit for SetLoadExt
−
Reset is carried out when SetLoadExt=0 (C0.5)
PF
Powerfail — A Loss of Field Power Supply is Reported
1:
Field voltage is < 5
V
0:
Field voltage is > 20.4 V
After a power failure, all cam windows are set to 0.
The counter reading is set to 0.
0
Reserved