Table 34: Control byte C1, All Versions, Except 750-637/000-004
Control Byte C1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Enable Ref
Set
Cam2
Set
Cam1
Dis
Cam2
Dis
Cam1
MapPZD
MapPZD
MapPZD
Coding of Process Data
MapPZD
Coding of Process Data
DisCam1
Inhibit Cam Output 1
0:
Cam output 1 enabled.
1:
Cam output 1 inhibited.
DisCam2
Inhibit Cam Output 2
0:
Cam output 2 enabled.
1:
Cam output 2 inhibited.
SetCam1
Apply Cam Output 1
Positive edge: Set value applied as lower comparison value N1_LO for
cam output 1 (N1).
Negative edge Set value applied as the upper comparison value N1_HI
for cam output 1 (N1).
SetCam2
Apply Cam Output 2
Positive edge: Set value applied as lower comparison value N2_LO for
cam output 2 (N2).
Negative edge Set value applied as the upper comparison value N2_HI
for cam output 2 (N2).
EnableRef
Enable REF Input
The control system sets the EnableRef bit
The control system must enable EN_LATC (C0.0) or
EN_LAT_EXT (C0.1) with a positive edge
A positive edge is generated at input REF
After this, the next positive edge at input C or LATCH will
result in a capture or preload event
0