WAGO I/O System 750
Function Description 45
750-637 Incremental Encoder Interfaces
Manual
Version 1.6.1
Public
Table 36: Function Description – Inputs
Input
Description
I/O Module
Function
GATE
GATE input,
24 V
750-637
The counting process is
disabled when 24 V is
applied to the GATE input.
750-637/000-001
750-637/000-002
750-637/000-003
750-637/000-004
The counting process is
disabled when 24 V is
applied to the GATE input.
The counter is enabled
when 0 V is present at the
GATE input, or when the
input is open.
This allocation can be
inverted by a control bit.
REF
REF input,
24 V
750-637
During a reference run the
index impulse is only
evaluated when an
additional sensor signal
(REF) is present.
750-637/000-001
750-637/000-002
750-637/000-003
REF input
750-637/000-004 The counter is set to 0 on a
positive edge for REF
Shield
Shielding
750-637
Connection for shielding of
the encoder line.
The shield (screen) is
directly connected to the
DIN rail.
750-637/000-001
750-637/000-002
750-637/000-003
750-637/000-004
+24 V
Supply voltage
750-637
24 V supply voltage for the
I/O module
750-637/000-001
750-637/000-002
750-637/000-003
750-637/000-004
0 V
Ground
750-637
Ground for the 24 V power
supply and encoder signals,
connected internally with
terminal V
0
750-637/000-003
750-637/000-001 Ground for 24 V supply
voltage
750-637/000-002 Ground for 24 V power
supply and encoder signals
750-637/000-004
V
e
(+5 V) Supply voltage
750-637
5 V supply voltage for
encoder
V
0
(0 V)
Ground
750-637
Ground for encoder signals
and power supply
connected internally with