22 Device Description
WAGO-I/O-SYSTEM 750
750-658 CAN Gateway
Manual
Version 1.2.1, valid from FW/HW-Version 01/01
4.2.3
CAGE CLAMP
®
Connectors
Figure 4: CAGE CLAMP
®
Connectors
Table 7: Legend for Figure “CAGE CLAMP
®
Connectors“
Designation Connector Function
CAN-H
1
CAN high
CAN-GND
2
CAN ground
0 V
3
Supply voltage 0 V
Shield
4
Shield connection (DIN rail)
CAN-L
5
CAN low
+24 V
6
Supply v24 V
Shield
(screen)
8
Shield connection (DIN rail)
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.