WAGO-I/O-SYSTEM 750
Configuration and Parameterization 63
750-658 CAN Gateway
Manual
Version 1.2.1, valid from FW/HW-Version 01/01
-
[Fix] button
: If the button is active, the entered value is copied to the
user data byte of the CAN telegram as a fixed value.
-
IDE
checkbox: If the checkbox is selected, CAN telegrams of type
"2.0B Extended" are sent with 29-bit identifier. If the checkbox is not
selected, CAN telegrams of type "2.0A Standard" are sent with 11-bit
identifier.
-
RTR
checkbox: If the checkbox is selected, CAN telegrams are sent
with activated "Remote Transmit Request Bit". If the checkbox is not
selected, data telegrams are sent.
-
Send on change
checkbox: If the checkbox is selected, a CAN
telegram can be generated and sent if the respective byte changes in
the process image of the output.
-
Send group
drop-down list: The selected CAN telegram can be
assigned to one or 8 send groups.
-
Cycle time (ms)
input field: The cycle time can be entered here. If the
value set is greater than 0 ms, the selected CAN telegram is generated
and sent when the time has elapsed.
-
[Add]
button: Adds the created mapping rule to the list of mapping
rules and closes the dialog.
-
[Cancel]
button: Cancels the process and closes the dialog.
Figure 31: "Add mapping rule" Dialog