Configuration and Parameterization 67
750-658 CAN Gateway
Manual
Version 1.2.1, valid from FW/HW-Version 01/01
9.1.8
"Filter" Dialog
With 6 configurable pass-through filters, the bandwidth of received CAN
telegrams for the user can be limited to specific ranges. This saves resources on
the control level and in the I/O module.
Figure 35: Selecting a Filter
To select a filter, proceed as follows:
1.
Select one or more of 6 pass-through filters. Activate the respective
"Activated" checkbox after the filter.
2.
Specify the upper and lower limits for the selected filter. Enter the
respective values in the "Lower CAN ID" and "Upper CAN ID" input fields.
3.
Specify whether received telegrams of the same CAN ID should be
overwritten or saved:
• Select "Overwrite" if the received telegrams with the same CAN ID
should be overwritten. This requires that the received telegram has not
yet been forwarded to the controller.
• Select "Keep All" if received telegrams should be forwarded
sequentially to the controller.
4.
Click the
[Write]
button.