WAGO-I/O-SYSTEM 750
Appendix 97
750-658 CAN Gateway
Manual
Version 1.2.1, valid from FW/HW-Version 01/01
Table 50: Expanded Configuration, Basic Structure of Tables 100 … 144
Reg
.
Description
Acceptable
value range
Default
standard value
0
CAN ID MSW
0x0000 … 0xFFFF
0xFFFF
1
CAN ID LSW
0x0000 … 0xFFFF
0xFFFF
2
IDE_RTR_DLC_SEN
DGROUP_SOC
0x0000...0x1FFF
0x0000
3
TAKE_FROM_PDOU
T_OR_FIXED_VALU
E
0x0000 … 0xFFFF
0x0000
4
CAN_PAYLOAD_DATA_1_0
0x0000 … 0xFFFF
0x0000
5
CAN_PAYLOAD_DATA_3_2
0x0000 … 0xFFFF
0x0000
6
CAN_PAYLOAD_DATA_5_4
0x0000 … 0xFFFF
0x0000
7
CAN_PAYLOAD_DATA_7_6
0x0000 … 0xFFFF
0x0000
8
SEND_CYCLE_TIME
0x0000 … 0xFFFF
0x0000
Register 0 and 1 save the CAN ID.
Table 51: Expanded Configuration, Tables 100 … 144, Register 0 … 1: CAN ID
Register
bits
Value range /
Possible values
Description
0.0 … 0.12 0x0000...0x1FFF
Top 13 bits (Bit 16 … 29) of the mapped
CAN telegram.
0.13 … 0.14 0x0
Reserved
0.15
0x0
Table configuration active
0x1
Table configuration inactive. Subsequent
tables will be ignored by the module.
1.0 … 1.15 0x0000 … 0xFFFF
Bottom 16 bits of the mapped CAN
telegram
Register 2 saves the parameters which define the transmission conditions and
the status bits contained in the telegram.