98 Appendix
WAGO-I/O-SYSTEM 750
750-658 CAN Gateway
Manual
Version 1.2.1, valid from FW/HW-Version 01/01
Table 52: Expanded Configuration, Tables 100 … 144, Register 2:
IDE_RTR_DLC_SENDGROUP_SOC
Register
bits
Value range /
Possible values
Description
2.0 … 2.3
0x0
CAN telegram not assigned to a
transmission group.
0x1, 0x8,
CAN telegram assigned to transmission
group 1 … 8.
0x9 … 0xF
Reserved
2.4 … 2.7
0x0, 0x8,
CAN telegram has payload data length 0 …
8 [Byte]
0x9 … 0xF
Reserved
2.8
0x0
CAN telegram is a data frame (RTR = 0)
0x1
CAN telegram is a "Remote Transmit
Request Frame" (RTR = 1)
2.9
0x0
CAN telegram is of type Standard 2.0 A
0x1
CAN telegram is of type Extended 2.0 B
2.10
0x0
"Send On Change" deactivated
0x1
"Send On Change" activated
2.11 … 2.15 0x0
Reserved
Register 3 saves the parameters that define the source (process image of output
or Register 4) from which the payload data byte values originated.
Table 53: Expanded Configuration, Tables 100 … 144, Register 3:
TAKE_FROM_PDOUT_OR_FIXED_VALUE
Register
bits
Value range /
Possible values
Description
3.0
0x0
CAN payload data byte 0 is a fixed value.
0x1
CAN payload data byte 0 is a variable value
and is copied/taken from the PIO.
…
…
…
3.7
0x0
CAN payload data byte 7 is a fixed value.
0x1
CAN payload data byte 7 is a variable value
and is copied/taken from the PIO.
4.0 … 4.7
0x0
Reserved
Register 4 … 7 save the values for the payload data bytes 0 … 7, or the offset at
which the values in this process image are set. Register 4 saves the value for
payload data byte 0 … 1.