WAGO-I/O-SYSTEM 750
Diagnostics 335
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
12.2.4 Meaning of Blink Codes and Procedures for
Troubleshooting
This section describes the diagnostics presented as blink codes via the MS
LEDs.
If the diagnostics cannot be cleared by the measured specified for them, contact
WAGO support. Be ready to explain to them the blink code that is displayed.
Phone: +49 571 887 555
Fax:
+49 571 887 8555
E-mail:
Table 240: Overview of MS-LED Error Codes
Error Code Explanation
1
Configuration error
Table 241: Error Code 1, Explanation of Blink Codes and Procedures for Troubleshooting
Error
Argument
Cause
Remedy
5
Error when
synchronizing the
controller
configuration with the
internal data bus
- Check the information of the
connected I/O modules in the
CODESYS controller configuration.
- Adjust this to match the I/O module
that is actually inserted.
- Recompile the project.
- Reload the project into the controller.