WAGO-I/O-SYSTEM 750
Service 339
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
13.3 Firmware Changes
Obtain documentation appropriate for the firmware target version!
A firmware upgrade or downgrade can modify, remove or add controller
properties and functions. As a result, described properties or functions of the
controller may not be available or available properties or functions may not be
described in the documentation. Therefore, use only documentation appropriate
for the target firmware after an upgrade/downgrade.
If you have any questions, feel free to contact our WAGO Support.
13.3.1 Perform Firmware Upgrade
Do not switch the controller off!
The controller can be damaged by interrupting the upgrade process.
Do not switch the controller off during the upgrade process and do not disconnect
the power supply!
Proceed as follows if you want to upgrade the controller to a later firmware
version:
1.
Save your application and the controller settings.
2.
Switch off the controller.
3.
Insert the memory card with the new firmware image into the memory card
slot.
4.
Switch on the controller.
5.
After booting the controller, launch the WBM “Create Boot Image” page
(you may have to temporarily change the IP address).
6.
Create a new boot image on the internal memory.
7.
Switch off the controller after completing the process.
8.
Remove the memory card.
9.
Switch on the controller.
The controller can now be started with the new firmware version.