WAGO-I/O-SYSTEM 750
Programming the PFC using WAGO-I/O-PRO 157
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Figure 61: Dialog window "Communication parameters"
6.
In the selection window, mark the required driver in the right side of the
window, Serial (RS-232) 3S Serial RS-232 driver, to configure the serial
link between the PC and the controller.
The following properties for the serial port are shown in the center dialog
window:
•
Port:
COM1
•
Baud
rate:
19200
•
Parity:
Even
•
Stop-bits:
1
•
Motorola byte order:
No
7.
If necessary, change the entries according to the above values by clicking on
the respective value and editing it.
8.
Confirm these settings by clicking
OK
The RS-232 port is now configured for transferring the application.
Pos: 82.69 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/In WAGO-I/O-PRO programmieren/Online, Einloggen, Bootprojekt erzeugen, Starten der Programmabarbeitung @ 4\mod_1242106439171_21.doc @ 32920 @ @ 1
9. Under
Online
, click the menu item
Login
to log in to the controller
The WAGO-I/O-
PRO
Server is active during online operation. The
communication parameters can not be called up during this time.
Depending on whether a program is already present in the controller, a window
will appear asking whether a (new) program should be loaded.
10. Respond
with
Yes
to load the current program.
11. In
menu
Online,
click on
Create Boot project.
You compiled project will also be executed by this method, if you restart the
controller or if there is a power failure.