WAGO-I/O-SYSTEM 750
Appendix 379
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 123 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/Anhang - Überschrift 1 @ 4\mod_1239874070437_21.doc @ 30560 @ 1 @ 1
16 Appendix
Pos: 124.1 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/SNMP (MIB)/MIB-II-Gruppen - System Group @ 4\mod_1237882031312_21.doc @ 28900 @ 23 @ 1
16.1
MIB II Groups
16.1.1 System Group
The system group contains general information about the coupler/controller.
Table 417: MIB II – System group
Identifier
Entry
Access Description
1.3.6.1.2.1.1.1
sysDescr
R
This entry contains the device identification. The
object has a fixed code (e.g., "WAGO 750-841")
1.3.6.1.2.1.1.2
sysObjectID
R
This entry contains the manufacturer's authorization
identification.
1.3.6.1.2.1.1.3
sysUpTime
R
This entry contains the time (in hundredths of a
second) since the management unit has been last
reset.
1.3.6.1.2.1.1.4
sysContakt
R/W This entry contains the identification and contact
information for the system contact person.
1.3.6.1.2.1.1.5
sysName
R/W This entry contains the administration-assigned
device name.
1.3.6.1.2.1.1.6
sysLocation
R/W This entry contains the node’s physical location.
1.3.6.1.2.1.1.7
sysServices
R
This entry designates the quantity of services that
this coupler/controller contains.