WAGO-I/O-SYSTEM 750
System Description
33
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 17.13.32 /Serie 750 (WAGO-I/O-SYSTEM)/Systembeschreibung/Versorgung/Ergänzende Einspeisungsvorschriften (Standard) @ 3\mod_1232950080218_21.doc @ 26684 @ 3 @ 1
3.6.4
Supplementary Power Supply Regulations
The WAGO-I/O-SYSTEM 750 can also be used in shipbuilding or offshore and
onshore areas of work (e. g. working platforms, loading plants). This is
demonstrated by complying with the standards of influential classification
companies such as Germanischer Lloyd and Lloyds Register.
Filter modules for 24-volt supply are required for the certified operation of the
system.
Table 5: Filter modules for 24-volt supply
Item No. Name
Description
750-626
Supply Filter Filter module for system supply and field supply (24 V,
0 V), i. e. for fieldbus coupler/controller and bus power
supply (750-613)
750-624
Supply Filter Filter module for the 24 V- field supply
(750-602, 750-601, 750-610)
Therefore, the following power supply concept must be absolutely complied with.
Figure 15: Power supply concept
Note
Additional supply module as ground (earth) conductor/fuse protection!
You must only use another potential power terminal 750-601/602/610 behind the
filter terminal 750-626 if you need the protective earth conductor on the lower
power contact or if you require a fuse protection.
Pos: 17.13.33 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1