52
Appendix
WAGO-I/O-SYSTEM 758
758-915
Bluetooth
®
ETHERNET Gateway
Manual
Version 1.1.0, applicable from FW/HW Version 01/01
8
Appendix
8.1
Sample Configurations
8.1.1
Preparation
Reset the WEG prior to the sample configuration!
Always
perform the following steps for the sample configuration
for all WEGs
involved
to reset the WEGs to the factory default settings.
1.
Connect the WEG to the power supply. If power is already applied,
disconnect it briefly and then re-activate power supply to the device.
2.
Within 5 seconds after connecting power
pressure Mode membrane
button.
The “A” LED lights up and the Configuration mode is active.
3.
Press the Mode membrane button
1 x
to select autoconfiguration procedure
2 (“Reset to Factory Default Settings”).
LED “B” lights up.
4.
Press and hold the Mode membrane button for
at least 2 seconds
until LED
“B” goes out.
The WEG has now been reset to the factory default settings.
8.1.2
WEG-WEG Bridge
Using two WEGs, a wireless link can be set up between spatially separated
ETHERNET segments. This is useful, for example, when laying of a cable may
not permitted or practical on account of structural conditions.
In this configuration example the WEGs fulfill the function of an ETHERNET
bridge, i.e., they make network nodes of both ETHERNET segments accessible to
one another by creating a transparent link on Layer 2 of the OSI reference model.