10.1
Setting Parameters
Select the
TO-PASS
®
telecontrol module to be configured from the project tree.
Select the
Addresses
option in order to enter the parameters for transmission to a
Web portal.
You can initially use our WAGO
TO-PASS
®
portal for test purposes.
To do this, enter "
" as the
Host address
and the value "80" as
the
Host port.
Enter "wago/saveTO-PASS.php" as the script name under
Script
(Values)
and/or under
Script (Logger)
.
Enter the information for your SIM card provider for
APN access
,
user name
and
password
(see also Section “Parameter setting” > “Addresses”).
Under
Special Functions
, select
Repetition Time
and set the
WEB Interval
for
the cyclic transmission to the Web portal, e.g., 5 minutes.
Select the messages that are also to be sent to the Web portal, and click the
[Internet]
button.
Communication as SMS or to the Web portal can be tested under the menu item
Processing > Test SMS/GPRS
. Click the
[Internet]
button and enter any text,
such as “TEST” in the field
Unstructured Text
. Then click
[Send]
. The reply
"Web Refresh = 0" should follow after approx. 20 seconds.
[MyTO-PASS]
. Enter
“test” as the user name and “test” as the password.
Now select your
TO-PASS
®
telecontrol module from the following list and click
the
[Display]
button.