110 WAGO TO-PASS® Web
WAGO-TO-PASS® 761
761-216 TO-PASS® Compact, 8 AI, Web, MODBUS
Manual
Version 2.0.0
10.3.1.1 Value Script FW 2.20 (Standard)
Table 49: Data format for value script FW 2.20 (Standard)
Index
Variable
Contents
Format
0
ID
Identity
Identity[8];Serial number[5]
1
PA
Parameter
Cycle time[4];Provider[5];Alarm counter[2]
2
TI
Date, time
YY/MM/DD,hh:mm:ss;
3
D1
Digital input 1
Value[1];Alarm[1]
4
D2
Digital input 2
Value[1];Alarm[1]
5
D3
Digital input 3
Value[1];Alarm[1]
6
D4
Digital input 4
Value[1];Alarm[1]
7
D5
Digital input 5
Value[1];Alarm[1]
8
D6
Digital input 6
Value[1];Alarm[1]
9
D7
Digital input 7
Value[1];Alarm[1]
10
D8
Digital input 8
Value[1];Alarm[1]
11
A1
Analog input 1
Value[6];Unit[5];Alarm[1]
12
A2
Analog input 2
Value[6];Unit[5];Alarm[1]
13
A3
Analog input 3
Value[6];Unit[5];Alarm[1]
14
A4
Analog input 4
Value[6];Unit[5];Alarm[1]
15
A5
Analog input 5
Value[6];Unit[5];Alarm[1]
16
A6
Analog input 6
Value[6];Unit[5];Alarm[1]
17
A7
Analog input 7
Value[6];Unit[5];Alarm[1]
18
A8
Analog input 8
Value[6];Unit[5];Alarm[1]
19*
US
Unstructured string
Data[40]
20**
MA
MODBUS alarm
Value[2];Status[2];Alarm[1]
21**
MV
MODBUS variables
64 x Value[4]
22***
PO
GPS position
String data[75]
* The variable is sent only if a Web refresh occurs via serial interface. ** The
variables are sent only if MODBUS is switched on.
*** The variable is sent only if the GPS functionality is available in the
TO-
PASS
®
telecontrol module.
Alarm marker for the multiplex function
When the multiplex function is used, the alarm markers for D1 to D4 are all '1' for
a multiplex alarm.