WAGO-TO-PASS® 761
Operation
85
761-216 TO-PASS® Compact, 8 AI, Web, MODBUS
Manual
Version 2.0.0
8.1.1
Remote Polling via SMS
For remote polling via SMS, send an SMS containing the text "State" to the
TO-
PASS
®
telecontrol module.
The
TO-PASS
®
telecontrol module responds promptly with an SMS to your
mobile phone containing all of the current process values.
Table 42: SMS format
Value transmitted:
Meaning
Module 1
Identity
10010011
Condition of the digital inputs 1 ... 8
(0 = not set, 1 = set)
+00.00mA
Analog input 1
+00.00mA
Analog input 2
+00.00mA
Analog input 3
+00.00mA
Analog input 4
+00.00mA
Analog input 5
+00.00mA
Analog input 6
+00.00mA
Analog input 7
+00.00mA
Analog input 8
0110
Condition of the digital outputs 1 ... 4
(0 = not set, 1 = set)
+00.00mA
Analog output 1
+00.00mA
Analog output 2
Normal Status
Status text or prepaid information (optional)
AC=99
Alarm counter
(displays the alarms that are still possible per hour).
The alarm counter only transmitted when enabled (Alarm
counter parameter in the Identifier dialog <> "0").
If at least one digital input is configured as a counter input, the counter status is
added to the SMS. The additional lines are added in front of the "Status text" line.
The counter status shows the last change that has occurred since the last SMS
transmission, or after a system start (independent of the value and logger status).
Example:
Table 43: Items added to SMS for counter inputs
Value transmitted
Explanation
0
Status counter 1 (no counter)
e34560000
Status counter 2 (counter active, counter value =
34560000)
C10000000
Status counter 3 (counter value changed, value =
10000000)
R0
Status counter 4 (counter reset, value = 0)