92
Operation
WAGO-TO-PASS® 761
761-216 TO-PASS® Compact, 8 AI, Web, MODBUS
Manual
Version 2.0.0
8.2.1
Telecontrol via SMS
8.2.1.1
Setting or Resetting a Digital Output
To set or reset a digital output, send an SMS with the text that is entered under
Activation text
or
Deactivation text
for the output to the TO-PASS
®
telecontrol
module. The
TO-PASS
®
telecontrol module acknowledges the command with an
SMS containing the identifier and the transmitted text.
Example:
Table 45: Example of parameters for
Set DO
Parameter
Setting
Activation text
DOUT1=1
Deactivation text
DOUT1=0
Turn-off time
00:00:00
Send an SMS with the text "DOUT1=1" to the
TO-PASS
®
telecontrol module to
switch on output 1. The
TO-PASS
®
telecontrol module acknowledges the
command with an SMS with the identifier and the text "DOUT1=1 OK!".
Send an SMS with the text "DOUT1=0" to the
TO-PASS
®
telecontrol module to
switch off output 1. The
TO-PASS
®
telecontrol module acknowledges the
command with an SMS with the identifier and the text "DOUT1=0 OK!"