94
Operation
WAGO-TO-PASS® 761
761-216 TO-PASS® Compact, 8 AI, Web, MODBUS
Manual
Version 2.0.0
8.2.1.3
Changing the Counter Value or Status
To change the value or the status of a counter, send an SMS containing the text
"Counter" and the corresponding control commands (more than one can be sent)
to the
TO-PASS
®
telecontrol module.
The control commands identify the counter input and the actual command.
Table 47: Control commands for counters
Control command Function
Cx= (x: 1 ... 4)
Select counter 1 ... 4
E
Activate counter
D
Deactivate counter
R
Reset counter
n (e.g., 500)
Set counter value
Control commands must be concluded with a semicolon (";").
The
TO-PASS
®
telecontrol module acknowledges the command with an SMS
containing the identifier and the transmitted text.
Example:
To activate Counter 2 and set it to 500, and to also deactivate Counter 3, send an
SMS containing the text "Counter: C2=E C2=500 C3=D;" to the
TO-PASS
®
telecontrol module.
The
TO-PASS
®
telecontrol module acknowledges the command with an SMS
containing the identifier and the text "COUNTER: OK!".